Fire resistance and smoke control classifications for construction products

Back to the product page

Fire resistance and smoke control classifications for construction products

What do E, EW, EI, EI₁, EI₂, Sa3, Sa4, S200 and the Swedish A-classes mean?

Fire-rated doors and partitions help limit the spread of fire. Markings such as EI₂60 and Sa3 identify a performance class; the product documentation defines the configuration and conditions it covers. This guide explains the key designations without confusing fire resistance with smoke control.

The key point: a fire-resistant door is not automatically smoke-tight, and a smoke-control door is not automatically fire-resistant. These are separate characteristics, demonstrated by different tests.

Class What it tells you
E – Integrity Limits the passage of flames and hot gases. It does not set a temperature-rise limit on the unexposed side.
EW – Integrity + radiation control Meets E and limits radiant heat flux to 15 kW/m², measured using the arrangement specified in the test standard. [1, 12]
EI – Integrity + insulation Meets E and limits temperature rise on the side away from the fire.

 

The number indicates the classification period under standard fire-test conditions. For example, E60, EW60 and EI60 mean 60 minutes for the relevant criteria, not a guaranteed safe duration in every real fire.

For non-loadbearing walls and similar separating elements, EI limits the average temperature rise on the unexposed side to 140 °C and the maximum rise to 180 °C, assessed as specified in the test standard. These are rises above the initial temperature, not absolute surface temperatures. Such walls use EI without the subscript 1 or 2. [1]

EEWEI

For doorsets, shutters and openable windows, the insulation assessment distinguishes EI₁ from EI₂. Both assess the door leaf and frame, but the edge zones and frame criteria differ. For the same classification period, EI₁ is more stringent.

Both classes: the average temperature rise on the assessed door-leaf surface is limited to 140 °C and the maximum rise to 180 °C. The frame is assessed separately.

EI₁ – More stringent EI₂ – Less stringent
Door-leaf edge zone excluded from temperature assessment 25 mm 100 mm
Maximum temperature rise at specified frame locations 180 °C 360 °C

 

The edge-zone widths are measured from the visible border of the door leaf. The 360 °C limit applies only to the specified frame measurement locations, not to the door leaf in general. A classification report may, for example, confirm EI₁45 and EI₂60 for the same door. [1, clause 5.2.3.3] [10]

EI₁EI₂

Yes. Different performance criteria can be satisfied for different periods. A single assessed configuration might, for example, be classified EI30 / EW60 / E120:

EI30 = integrity and insulation for 30 minutes; EW60 = integrity and radiation control for 60 minutes; E120 = integrity for 120 minutes.

This is an example, not a claim about every product. Each class must be supported by the classification report and cover the actual configuration, dimensions and installation. [1]

For doorsets, fire resistance is tested to EN 1634-1 and smoke leakage to EN 1634-3. EN 13501-2 defines the classifications. Smoke control does not mean zero leakage: the class sets a limit under specified test conditions. [1–3, 11]

Class Test conditions and leakage limit
Sa Ambient temperature (approximately 20 °C), pressure differences up to 25 Pa: no more than 3 m³/h per metre of assessed gap.
S200 Ambient temperature and 200 °C, pressure differences up to 50 Pa: no more than 20 m³/h for a single-leaf or 30 m³/h for a double-leaf doorset.

Does the bottom gap count?

EN 13501-2:2023 supplements Sa with 3 or 4 to identify whether bottom-edge leakage is included:

Sa3: leakage beneath the door leaf is excluded. Sa4: leakage beneath the door leaf is included with leakage at the other edges. For double-leaf doors, the meeting-edge gap is also assessed; its length is counted once.

The earlier Sa designation corresponds by default to Sa3, not Sa4. The tested threshold or drop-down seal can therefore be important. A low-threshold or threshold-free design is possible where the documented solution meets the required class. [1, clause 7.5.5.3.4]

EI₂60 Sa4 indicates both fire resistance and ambient-temperature smoke control. S200 has different leakage limits and does not automatically establish Sa3 or Sa4. Check the documents for every required property, including self-closing where applicable. [1]

SaS200Sa3Sa4

Swedish A30 and A60 are historical building-product fire classes, not the IMO A-classes used for ships. Their assessment is based on earlier Swedish criteria; historical test methods include SS 24827 / NT FIRE 008. [8, 9]

RISE type approvals may cover A30 or A60 alongside EI30, EI60 or EI₂30. This does not make all approved configurations identical or allow an A-class to be relabelled as an EN EI-class. Check the assessment basis, drawings and approval conditions for the actual product. EI without a subscript is not, by itself, evidence of a historical Swedish classification. [1, 8]

Under the previous BBR guidance, A-classified doors could, in specified circumstances, be used where an EI door with the same time requirement was required. This was national acceptance, not an EN 13501-2 classification. Historical assessment routes also covered certain walls and fixed windows, not only internal doors. [7, 8]

CE marking: external and internal doors

External pedestrian doorsets within the scope of EN 14351-1 are generally CE-marked under that standard. For fire resistance and/or smoke control characteristics, EN 16034 is used together with EN 14351-1. EN 16034 alone is not a CE-marking basis. National type approval cannot replace mandatory CE marking. [4, 6]

Internal pedestrian fire doors do not currently have a harmonised product-standard route to CE marking. In Sweden, appropriate national product documentation may be used; RISE type approval is one option, not a universal requirement. Eligible products can follow the European Technical Assessment (ETA) route to CE marking. Obtaining an ETA is voluntary, but marketing a product on that basis requires the applicable assessment and verification, a Declaration of Performance and CE marking. A classification report alone does not replace these steps. [5, 6]

A30A60

Boverket’s new fire safety rules took effect on 1 July 2025. Eligible projects, including building-permit applications received by the municipality before 1 July 2026, could use the previous BBR framework under the transition rules. Applications received from 1 July 2026 generally follow the new rules. The transition concerns the regulatory framework as a whole, not a free choice of individual old and new provisions. [7]

RISE CR 062 limits a specified historical national assessment route for internal doors to 1 July 2029. This is not a general expiry date for all fire products. A project’s right to use older building rules does not extend a product certificate. The approval’s scope and actual validity must be checked separately; references to 2031 do not renew all certificates automatically. [8]

A specific Swedish insulation alternative

Boverket’s regulation BFS 2024:7, Chapter 1, section 6, allows a national insulation alternative for doors made of non-combustible materials: an average temperature rise of up to 280 °C and a maximum individual rise of 330 °C. Other applicable requirements still apply. This is not an EN EI classification and does not replace the EN performance required for CE marking. Its suitability must be verified for the intended use; analytical fire safety design may also be relevant in some cases. [7]

Check the class required by the project, the product’s current classification or approval, permitted sizes and components, supporting wall, installation and fire-exposure direction. Confirm smoke control and self-closing separately where required. Changes to glass, locks, seals, thresholds or the overall configuration must remain within the documented field of application.

Need help choosing a solution? Tammer can help you check the required class and the supporting documentation for your project.

Standard links lead to the official EVS catalogue; the full standards contain the normative requirements. References [10]-[12] provide supplementary European technical explanations and do not replace the standards.

[1] EN 13501-2:2023 – Classification standard, clauses 5.2.2-5.2.4, 6.5.1 and 7.5.5.3.4. Official edition and scope: EVS catalogue.

[2] EN 1634-1:2014+A1:2018 – Fire resistance tests for doors, shutters and openable windows. Official EVS catalogue.

[3] EN 1634-3:2004 (AC:2006) – Smoke leakage test method for door and shutter assemblies. Official EVS catalogue.

[4] EN 14351-1:2006+A2:2016 and EN 16034:2014 – Product standards. The EVS listing for EN 16034 expressly states the requirement for combined application.

[5] EOTA: ETA and CE marking – Official FAQs; EADs 020029-00-1102 and 020062-00-1102 for internal steel and steel-profile doorsets. EAD register.

[6] Boverket: Ditt ansvar som byggherre – CE marking, voluntary type approval and product suitability in Sweden.

[7] Boverket: Brandtekniska klasser – BFS 2024:7, Chapter 1, sections 6 and 12, as amended; previous BBR section 5:534. BFS 2024:14 transition provisions.

[8] RISE CR 062, 9 June 2025 – Certification rule for type approval of fire products, section 4.1.1 and Annex 1. Official English translation; Swedish original prevails.

[9] SIS: SS 24827 / NT FIRE 008 – Historical test method. National assessment: Riktlinjer för typgodkännande brandskydd, 1993:2, edition 2, cited by RISE CR 062.

[10] Italian Ministry of the Interior: D.M. 21 June 2004 – Annex B, p. 11, published by Vigili del Fuoco. Supporting technical explanation of I₁/I₂; not a substitute for EN 13501-2:2023 or a legal basis for projects outside Italy.

[11] SKG-IKOB, Netherlands: EN 1634-3 smoke testing – Accredited laboratory’s explanation of test temperatures, pressure differences and Sa/S200 leakage limits. The current Sa3/Sa4 notation is defined by [1].

[12] Buildwise, Belgium: Magazine, November-December 2022 – Fire-door article, p. 9: supporting explanation of the EW radiation limit. Cited for that technical criterion, not for current CE-marking requirements.

Regulatory information checked: 28 October 2026.